ABB OT160E03CP 160A 3-Pole Change-Over Switch
The OT160E03CP is a 160A, 3-pole manual change-over switch used to transfer a load between two power sources, such as mains and generator supply. It includes a black plastic IP65 I-0-II pistol type handle, shaft and bolt set for cable connection, making it ready for base mounting in distribution panels. With door interlock in the I and II positions and padlocking capability in the 0-position, it is a reliable choice for backup power switching in UAE commercial and industrial facilities where generator changeover is common.
Key Features
- 160A rated 3-pole manual change-over switch for reliable source-to-source load transfer
- IP65 pistol type I-0-II handle providing dust and moisture resistance, well suited to UAE ambient conditions
- Door interlock in the I- and II- positions plus padlocking in the 0-position for enhanced operator safety
- Rated insulation voltage of 1000V and impulse withstand voltage of 12kV for robust electrical protection
- Genuine ABB quality
Technical Specifications
| Specification |
Details |
| Brand |
ABB |
| Model |
OT160E03CP |
| Poles |
3P |
| Rated Operational Current (AC-23A) |
160A (380–415V / 500V / 690V) |
| Rated Operational Voltage (Main Circuit) |
1000V |
| Rated Insulation Voltage (Ui) |
1000V |
| Rated Impulse Withstand Voltage (Uimp) |
12 kV |
| Rated Short-time Withstand Current (Icw) |
8 kA for 1s |
| Degree of Protection |
Front IP20 (handle IP65) |
| Handle Type |
Pistol type I-0-II, black |
| Mounting |
Base mounting |
| Terminal Type |
Screw Terminals |
| Transition Type |
Open |
| Pollution Degree |
3 |
| Net Weight |
3.1 kg |
Applications
- Manual transfer between mains and standby generator supply in commercial buildings
- Backup power switching for FM-managed facilities across the UAE
- Source changeover in industrial panels requiring door-interlocked safety
- Load transfer switching in retail, hospitality, and residential tower distribution boards
FAQ
-
Is this an MCB or an isolator?
It's an isolator (switch-disconnector), not an MCB. It has no overload or short-circuit protection — it only provides a manual on/off disconnect, and should be paired with separate MCBs or RCCBs for circuit protection.
-
What does 3-pole mean for this isolator?
3-pole means it switches all three phases on a three-phase supply.
-
Where should this isolator be installed?
Typically as the main incoming switch or a local isolation point ahead of the MCBs/RCCBs in a distribution board, so the whole board (or a section of it) can be isolated for maintenance without needing to trip individual breakers.
-
Can I install this myself?
No. This is trade-only distribution board equipment and must be installed and connected by a licensed electrician in accordance with local wiring regulations.
-
Can this isolator be used to switch a live circuit under load?
Isolators rated for on-load switching can do this within their utilisation category, but check the specific AC rating in the Technical Specifications table — an isolator is not a protective device and should not substitute for a circuit breaker.