ABB E204/80R 4-Pole 80A DIN Rail Isolator
The ABB E204/80R is a 4-pole modular switch-disconnector rated for 80A, designed for load commanding duties on DIN rail distribution boards in accordance with EN 60947-3. Its compact 4-module design and fast busbar removal without dismantling make it a practical choice for main isolation and load switching in UAE residential, commercial, and industrial panels.
Key Features
- 4-pole 80A modular isolator suitable for main load switching and isolation in DIN rail distribution boards
- Rated short-circuit breaking capacity of 25kA at 230/400V AC for reliable protection coordination
- Captive Pozidriv size 2 screws with recessed/slotted head for fast, secure terminal connections
- Supports add-on of up to 3 auxiliary contacts and a locking device for unauthorized ON/OFF operation
- Genuine ABB quality — manufactured to IEC/EN 60947-3 standard
Technical Specifications
| Specification |
Details |
| Brand |
ABB |
| Model |
E204/80R |
| Poles |
4P |
| Rated Current (In) |
80A |
| Rated Operational Voltage |
230/400V AC |
| Rated Short-Circuit Breaking Capacity (Ics) |
25kA |
| Voltage Protection Level (Up) |
4kV |
| Overvoltage Category |
IV |
| Degree of Protection |
IP10 |
| Mounting |
DIN Rail (acc. to DIN 43880) |
| Installation Width |
4 modular spacings (70 mm) |
| Standard |
IEC/EN 60947-3 |
| Weight |
0.39 kg |
Applications
- Main isolation switching in residential and commercial distribution boards
- Load switching and disconnection in modular DIN rail panel assemblies
- Safe isolation points for maintenance in FM and facilities operations
- Panel builder projects requiring compact 4-pole switch-disconnectors with auxiliary contact options
FAQ
-
Is this an MCB or an isolator?
It's an isolator (switch-disconnector), not an MCB. It has no overload or short-circuit protection — it only provides a manual on/off disconnect, and should be paired with separate MCBs or RCCBs for circuit protection.
-
What does 4-pole mean for this isolator?
4-pole means it switches all three phases plus neutral, for supplies where the neutral must also be isolated.
-
Where should this isolator be installed?
Typically as the main incoming switch or a local isolation point ahead of the MCBs/RCCBs in a distribution board, so the whole board (or a section of it) can be isolated for maintenance without needing to trip individual breakers.
-
Can I install this myself?
No. This is trade-only distribution board equipment and must be installed and connected by a licensed electrician in accordance with local wiring regulations.
-
Can this isolator be used to switch a live circuit under load?
Isolators rated for on-load switching can do this within their utilisation category, but check the specific AC rating in the Technical Specifications table — an isolator is not a protective device and should not substitute for a circuit breaker.